XNX Universal Transmitter Technical Manual - Page 80

For XNX UNIVERSAL.

Loading ...
Loading ...
Loading ...
XNX Universal Transmitter
Section 2 - Installation and Operation
78
Figure 139. Modbus Options Screen
From the Set Fieldbus Address screen, select
. To set the
Fieldbus address, use the
switches to move to the desired
position and use
to select it. Use the switches to
decrement or increment the value until the desired value appears.
Use
to select the value and moves to the next setting.
Figure 140. Set Fieldbus Address and Address Value Screens
The communications baud rate can be set from this screen. Use
the switches to highlight the proper baud rate and select
.
Figure 141. Set Baud Rate Screens
Once the values for the Fieldbus address have been set, use
the
switches to navigate to the ‘ü’ then select it to save the
changes.
Figure 142. Accept Settings and Fieldbus Address Settings Accepted
Congure Security
CongureSecurityisusedtosetorresetthelevel1andlevel
2passcodesthatcontrolaccesstothecongurationmenusof
the XNX transmitter.
Figure 143. Congure Security Screens
Easy Reset from Main Status
The Easy Reset from Main Status option controls the ability
to reset faults, warnings, and alarms from the General Status
screen (see Section 1.4.2).
Use the switches and
to select the lock icon .TheLock/
Unlock screen will be displayed. Choose ‘Lock’ to prevent reset
without password access. The ‘Unlock’ choice allows resets
without requiring login or a passcode.
Figure 144. Lock/Unlock Screen