XNX Universal Transmitter Technical Manual - Page 123

For XNX UNIVERSAL.

Loading ...
Loading ...
Loading ...
XNX Universal Transmitter
Section 5 - Warnings/Faults
121
Note 3:
Subtypes Decimal Description
Fault 2
Event Bits
1 CRC error in safety critical RAM block
2 Error reloading safety critical RAM block from EEPROM
4 Error loading data from Personality board
8
Excel signal level has been below the low signal level
threshold for at least 24 hours
16 Excel beam blocked
32 Personality board error code > 0
64 Option board error code > 0
128 IR mA input > 1 mA and < 3.4 mA
256 IR mA input < 1.0 mA
512 IR forced 10 mA not within +/-1 mA
1024 gains from PGA don't match local copy
2048 error reading or writing EEPROM
4096 ECC reî››ex failure
8192 RAM test failure
16384 Program memory CRC failure
32768 Op code test failure
Fault 3
Event Bits
1 Interrupt integrity test failure
Loading ...