XNX Universal Transmitter
Section 5 - Warnings/Faults
124
Number Description Contents of Data Field
I025
Alarms Congured Non-Latching N/A
I026
Alarm Relays Congured Normally
Energized
N/A
I027
Alarm Relays Congured Normally De-
Energized.
N/A
I028
Fieldbus Address Changed New address (e.g. 15)
I029
Fieldbus Speed Changed New speed (e.g. 19200)
I030
Sensor Type Changed iCurrentCalGlobalID
I031
Gas Selection Changed iCurrentCalGlobalID
I032
Time For Beam Block Fault Changed iBlockFltTime
I033
Time For Fault Detection Changed iOtherFltTime
I034
Level For Low Signal Fault Changed fLowSignalLevel
I035
Invalid Path Length Written fPathLen
I036
Path Length Changed fPathLen
I037
mA for Inhibit Changed f_mA_Flt_Step[0]
I038
mA for Warning Changed f_mA_Flt_Step[1]
I039
mA for Overrange Changed f_mA_Flt_Step[2]
I040
mA for Fault Changed f_mA_Flt_Step[3]
I041
mA for Low Signal Changed f_mA_Flt_Step[4]
I042
mA for Blocked Beam Changed f_mA_Flt_Step[5]
I043
Concentration for mA Full Scale Changed fDisplayRange
I044
Instrument Id Changed N/A
I045
Measuring Units Changed iMeasurementUnits
I046
Alarm 1 Recongured for Increasing
Concentrations
N/A
I047
Alarm 1 Recongured for Depleting
Concentrations
N/A
5.3 Informational Messages
Number Description Contents of Data Field
I001
Unused
I002
Force Relay Mode Started Bitpattern for relays. (E.G. 7.0 ==All)
I003
Force Relay Mode Ended. N/A
I004
Force mA Mode Started Force current. (E.G. 20.0)
I005
Force mA Mode Ended N/A
I006
Short-Term Inhibit Started N/A
I007
Short-Term Inhibit Ended N/A
I008
Long-Term Inhibit Started N/A
I009
Long-Term Inhibit Ended N/A
I010
mA Output Recalibrated N/A
I011
Bump Test Started N/A
I012
Bump Test Timed Out N/A
I013
Bump Test Completed Concentration < Al1 Peak concentration observed
I014
Bump Test Completed
Al1 < Concentration < Al2
Peak concentration observed
I015
Bump Test Completed. Al2 < Concentration Peak concentration observed
I016
Zero Calibration Successful N/A
I017
Zero Calibration Failed Error code
I018
Calibrate Span Successful 1 of 2 Percent change in span factor from previous
I019
Calibrate Span Successful 2 of 2 Absolute span factor
I020
Calibrate Span Failed Error code
I021
Calibrate Span Timeout N/A
I022
Password Changed 1,2 or 3 (access level)
I023
Performing Soft Reset N/A
I024
Alarms Congured Latching N/A