XNX Universal Transmitter Technical Manual - Page 8

For XNX UNIVERSAL.

Loading ...
Loading ...
Loading ...
XNX Universal Transmitter
Introduction
6
WhenthetransmitterisequippedwiththeoptionalRemoteMountKit,
theremotesensormustbesecurelymountedinafixedposition.The
RemoteSensorkitisnotintendedtobeusedasahand-heldsensor.
Enclosuresofremotelymountedsensorscontainaluminum.Becareful
toavoidignitionhazardsduetoimpactorfrictionwheninstalledin
Zone1locations.
Installthejunctionboxaccordingtolocalcodesandmanufacturer’s
requirements.
Theenclosuresofremotelymounted705HTsensorscontain
aluminum.Becarefultoavoidignitionhazardsduetoimpactorfriction
wheninstalledinZone1locations.
PoweroffthetransmitterbeforechangingS3orS4.Bothswitches
mustbesetineitherSourceorSinkpriortoapplyingpower.
Minimumandmaximumcontrolleralarmlevelsshouldnotbeset
atlessthan10%orgreaterthan90%ofthefullscalerangeofthe
sensor.Limitsare60%LELor0.6mg/m
3
foragencyperformance
certification.
Whenconfiguringorcommunicatingwiththetransmitterusingthe
frontpaneldisplays,resumemonitoringbyexitingallmenusand
returningtotheGeneralStatusmenumanually.Notimeoutsare
invoked.
WhenselectinganewtargetgasforunitswithaSearchpointOptima
Plus,thesensormustberecalibrated.
XNXUniversalTransmitterscarryingUL/CSA/FMapprovalsthatare
configuredfordevicesmeasuring%LELwillnotallowadjustmentsto
thefullscalevalue.Therangeisfixedat100%.
Thereisapotentiallossofsensitivityduringexposuretohigh
concentrationsofH2S.Undertheseconditions,setthecontrolunitto
latchatoverrange.Instandaloneconfiguration,setalarmstolatching.
Whenresettingtheoverrangeoralarm,verifycorrectoperationofthe
transmitter.
Keepthepasswordsinasecureareatopreventunauthorizedaccess
tothetransmitter.Ifthepasswordsarelost,resettingtheXNX
transmitterwillrequireaservicetechnician.
WhentheXNXtransmitterisplacedinInhibitMode,alarmsare
silenced.Thiswillpreventanactualgaseventfrombeingreported.
InhibitModemustbelimitedtotestingandmaintenanceonly.Exit
InhibitModeaftertestingormaintenanceactivities.
Honeywellrecommendsperiodicbumptests(every30daysorin
accordancewithcustomersiteprocedures)tothesensortoinsure
properoperationandcompliancewiththefunctionalsafetyratingof
theinstallation.
Assometestgasesarehazardous,exhausttheflowhousingoutlettoa
safearea.DonotusetheXNXUniversalTransmitterinoxygen-enriched
atmospheres.(Inoxygen-enrichedatmospheres,theelectricalsafetyis
notgiven.)
Exposuretodesensitizingorcontaminatingsubstancesor
concentrationscausingoperationofanyalarmmayaffectsensor
sensitivity.Followingsuchevents,itisrecommendedtoverifysensor
performancebyperformingafunctionalgastest(bumptest).
Whenservicingorreplacingsensors,reducetheriskofignitionof
hazardousatmospherebydeclassifyingtheareaordisconnecting
theequipmentfromthesupplycircuitbeforeopeningthesensor
enclosure.Keeptheassemblytightlyclosedduringoperation.
Takeappropriateprecautionswhenusingtoxic,flammable,and
pressurizedcylinders.
Delaysresultingfromtransmissionerrorsbetweensensorand
transmitterextendresponsetimesT90bymorethanone-third.The
perioduntilfault
indicationis10seconds
.
TheHARTinterfaceissubjectofthisEC-typeexaminationcertificate
onlyforthepurposeofconfigurationandmaintenance.