XNX Universal Transmitter
Section 6 - Specications
132
6.2.3 EC Sensor Performance Data, DEKRA EXAM veried (see Section 6.3)
Gas Cartridge P/N
Selectable Full
Scale Range (Dis-
play and 4-20mA
Full Scale)
Default
Range
Range
Incre-
ments
Lower
Alarm
Limit
Lower
Detection
Limit
Zero
Variation
Selectable
Cal Gas
Range
Default Cal
Point
Response
Time (T50)
(sec)
T90 Response
T10 Recovery
Time (sec)
Accuracy
1
Operating Temperature Operating Humidity
Min Max Min Max
O
2
Oxygen XNXXSO1SS n/a 25.0 %Vol n/a 5.0%Vol 3.5 %Vol n/a
20.9 %Vol
(fixed)
20.9 %Vol T20 <10 <30 <+/-0.6 %Vol -30°C / -34°F 55°C /131°F 15% RH 90% RH
H
2
S
Hydrogen
Sulfide
XNXXSH1SS 10.0 to 50.0 ppm 15.0 ppm 0.1ppm 3.0 ppm 1.0 ppm 2.0 ppm
30 to 70%
of the
selected full
scale range
10 ppm <20 <30 <+/-0.3 ppm -40°C / -40°F 55°C / 131°F 15% RH 90% RH
H
2
S (High)
Hydrogen
Sulfide
XNXXSH2SS 50 to 500 ppm 100 ppm 10 ppm 5 ppm 1 ppm 2 ppm 50 ppm <20 <30 <+/-5 ppm -40°C / -40°F 55°C / 131°F 15% RH 90% RH
CO
Carbon
Monoxide
XNXXSC1SS 100 to 500 ppm 300 ppm 100 ppm 15 ppm 5 ppm 10 ppm 100 ppm <15 <30 <+/-2 ppm -40°C / -40°F 55°C / 131°F 15% RH 90% RH
FOOTNOTE:
1.AccuracyofreadingatdefaultAlarm1concentration(typically10%FSordefinedminimumalarmlevelsetting,whicheverisgreater)whenoperatedatdefaultfullscale.
NOTES:
• SensordriftbetweenLDLandnegativedriftfaultlimits(typcially>negativezerovariation)appearas0onthedisplayandoutputsofthedevice.
• Long-termdrift:XNXXSC1SS<5%/year,XNXXSO1SS<4%/year,XNXXSH1SSandXNXXSH2SS<2%/month.
• Performanceguresaremeasuredbytestunitscalibratedat50%offullscale,atambientconditionsof20°C,50%RH,withtheECweatherproofcoverattached.
• OperatingtheXNXECsensoratextendedtemperaturerangesforaprolongedtimeperiodexceeding12hoursmaycausedeteriorationinsensorperformanceandshorten
sensorlife.ExtendedtemperaturerangesforXNXECsensorcartridgesare-40°Cto-20°C.
• Barometric pressure effects on the O
2
sensor: The output from the O
2
sensor has pressure effects of <0.1% change of output per % change in pressure. When the barometric
pressure changes by ±20%, the output from the O
2
sensorchanges<±0.4%Vol.However,theoxygensensorshowstransientbehaviorwhensubjectedtoarapidchangein
ambientpressureduetoeitherweatheroraltitude.Forexample,a10KPainstantaneouspositivepressurestepchangemaycauseanoverscalealarmconditionforaperiod
of about 12 seconds.
• Responsetimesmayincreaseatlowertemperatures.
• ContactHoneywellAnalyticsforanyadditionaldataordetails.