Configure "Door Forced Open" Alarm Feature: 103
1
Press Then
2
Enter Alarm Option (0-2). Then (#)
Option 0=Disabled
Option 1= Enabled Relays will activate until relay time expires
(See Step 2 Set Each Relay’s “Activation Time” on page 23 for more information.)
Option 2=Enabled Relays will activate until the alarm condition clears
3
Activate (1) or Deactivate (0) Relays (0000-1111). Then (#) (1st digit=Relay 4, 2nd digit=Relay 3, etc.).
When enabled, doors that are forced open will trigger an alarm. The alarm will activate the relays you specify.
The relays can remain active until the relay time expires or until the alarm condition clears.
Factory Setting: Disabled
Setting "Strikes and Out" (Number of Entry Code Attempts before
Disabling Unit):
17
1
Press Then
2
Enter Maximum Number of Strikes and Outs
Allowed (0-5). Then (#)
0=Disabled
The "Strikes and Out" feature prohibits unauthorized persons from guessing an entry code or the unit password
and entering programming mode. Anyone entering an entry code or password will have a set number of times to
correctly enter their code. Each time the code is entered incorrectly, it is a "strike". After "x" number of "strikes", the
system will disallow code entry at the unit for 3 minutes. Factory Setting: 3 Times
1 2 3
Relay 4
Deact Deact DeactActivate
Relay 3 Relay 2 Relay 1
When a "Door Held Open" alarm condition occurs, Relay "4" will activate until the relay condition
expires. If the alarm relay controls a siren, the siren will sound until the relay time expires.
Configure "Strikes and Out" Alarm Feature: 104
When enabled, an alarm will trigger if someone enters an erroneous entry code or the unit password on the
unit keypad more than the maximum number allowed (see above). The alarm will activate the relays you
specify. The relays can remain active until the relay time expires or until the alarm condition clears.
Factory Setting: Disabled
When a "Strikes and Out" alarm condition occurs, Relay "4" will activate until the relay time expires.
1
Press Then
2
Enter Alarm Option (0-2). Then (#)
Option 0=Disabled
Option 1= Enabled Relays will activate until relay time expires (See Step 2 Set Each Relay’s “Activation
Time” on page 23 for more information)
Option 2=Enabled Relays will activate until the alarm condition clears
3
Activate (1) or Deactivate (0) Relays (0000-1111). Then (#) (1st digit=Relay 4, 2nd digit=Relay 3, etc.)
EXAMPLE:
EXAMPLE:
1 2 3
Relay 4
Deact Deact DeactActivate
Relay 3 Relay 2 Relay 1