Environment
Contextual help of the web interface – 58
Action #1-3
1- Reboot the Network module.
2- Launch the discovery.
Symptom #2
The EMPs orange RJ45 LEDs are not blinking.
Possible causes
C#1: the EMP address switches are all set to 0.
C#2: the EMPs are daisy chained, the Modbus address is the same on the missing EMPs.
Action #2-1
1- Change the address of the EMPs to have different address and avoid all switches to 0.
Refer to the section Servicing the EMP>>>Defining EMPs address and termination>>>Manual addressing .
2- Disconnect and reconnect the USB to RS485 cable. The address change is only taken into account after an EMP power-up.
3- Launch the discovery,if it is still not ok, go to Action #2-2.
Action #2-2
1- Reboot the Network module.
Refer to the section
Contextual help>>>Maintenance>>>Services>>>Reboot .
2- Launch the discovery.
3.6.1.5.1 For other issues
3.6.2 Alarm configuration
For details on other issues, see the Troubleshooting section.
Humidity, temperatures or dry contacts deactivated during commissioning are not displayed.
Gauge color code:
Green: Value inside thresholds.
Orange/Red: Value outside thresholds.
Grey: No thresholds provided by the device.