Default settings and possible parameters
Information – 180
Local certificates
Common name — Service + Hostname + selfsigned
Country — FR
State or Province — 38
City or Locality — Grenoble
Organization name — Eaton
Organization unit — Power quality
Contact email address — blank
Common name — 64 characters maximum
Country — Country code
State or Province —64 characters maximum
City or Locality —64 characters maximum
Organization name —64 characters maximum
Organization unit —64 characters maximum
Contact email address —64 characters maximum
7.3.2 Meters
Default settings and possible parameters - Meters
Default settingPossible parameters
Meters/LogsLog measures every—60sLog measures every — 3600s maximum
7.3.3 Sensors alarm configuration
Default settings and possible parameters - Environment Alarm configuration
Default settingPossible parameters
TemperatureEnabled—No
Low critical – 0°C/32°F
Low warning – 10°C/50°F
High warning – 70°C/158°F
High critical – 80°C/176°F
Enabled—No/Yes
low critical<low warning<high warning<high critical
HumidityEnabled—No
Low critical – 10%
Low warning – 20%
High warning – 80%
High critical – 90%
Enabled—No/Yes
0%<low critical<low warning<high warning<high
critical<100%