Protection
Contextual help of the web interface – 47
3.5.2.4 Access rights per profiles
AdministratorOperatorViewer
Protection/Agent settings
3.5.2.4.1 For other access rights
3.5.3 Shutdown on power outage
These setting are in conjunction with the shutdown agents andcontrol how the network module directs the shutdown of protected
servers and appliances. It gives the possibility to prioritize and schedule shutdown actions so that the IT system is powered down
in the correct order. For example, applications first, database servers next, and storage last. It is also possible to turn off some
outlets to reduce power consumption and get longer battery runtime for the most important devices.
The trigger in the diagram isthe moment whenthe shutdown sequence starts, and it is defined in theContextual
help>>>Protection>>>Scheduled shutdownor theContextual help>>>Protection>>>Shutdown on power
outagesections for each power source.
For other access rights, see the Information>>>Access rights per profiles section.
For examples on Powering down applications see theServicing the Network Management Module>>>Powering
down/up applications examples section.