Tripp Lite EVMAGU23X NEW Eaton G4 Universal-Input Managed PDU, 208V and 415/240V, 42 Outlets, Input Cable Sold Separately, 72-Inch 0U Vertical

Eaton G4 Gigabit Network Module GNM Firmware User Guide - Page 191

For EVMAGU23X NEW.

PDF File Manual, 231 pages, Read Online | Download pdf file

EVMAGU23X NEW photo
Loading ...
Loading ...
Loading ...
List of event codes
Information – 191
7.5.2 UPS(HID) alarm log codes
7.5.2.1 Critical
CodeSeverityActive messageNon-active messageAdvice
002CriticalInternal failureEnd of internal failureService required
004CriticalTemperature alarmTemperature OKCheck air conditioner
100CriticalRectifier fuse faultRectifier fuse OKService required
105CriticalInput AC module failureInput AC module OKService required
207CriticalBypass AC module failureBypass AC module OK-
208CriticalBypass overloadNo bypass overload-
305CriticalRectifier failureRectifier OKService required
306CriticalRectifier overloadRectifier OKReduce output load
308CriticalRectifier short circuitRectifier OKReduce output load
400CriticalDCDC converter failureDCDC converter OKService required
500CriticalBattery charger faultBattery charger OKService required
607CriticalBattery test failedBattery test OKCheck battery
60DCriticalNo batteryBattery presentCheck battery
61BCriticalBattery BMS faultBattery BMS OKCheck battery
629CriticalBattery voltage low criticalBatteryvoltage OKCheck battery
62BCriticalBattery voltage high criticalBatteryvoltage OKCheck battery
62DCriticalBattery charge current low criticalBatterycharge current OKCheck battery
62FCriticalBatterycharge current high criticalBatterycharge current OKCheck battery
631CriticalBattery discharge current low
critical
Batterydischarge current OKCheck battery
633CriticalBatterydischarge current high
critical
Batterydischarge current OKCheck battery
This table applies to all UPS except to the 9130 UPS.
To retrieve Alarm logs, navigate to Contextual help>>>Alarms section and press the Download alarms button.
Below codes are the one to be used to add "Exceptions on events notification" on email sending configurations.
Some zeros maybe added in front of the code when displayed in emails or logs.
Loading ...
Loading ...