Checking the current firmware version of the Network Module
Servicing the Network Management Module – 139
This will allow to restart sequentially the IT equipment on utility recovery.
4.3.3.2.2 Resulting setup
UPS provides outlets (Group 1 and Group 2) and a primary output.
Connections to UPS can be done as described below:
Group 1: Applications
Group 2: Database servers
Primary: Storage
4.3.3.3 Step 2: Power outage policy settings
4.3.3.3.1 Objective
Use load segment restart settings to define restart sequencing.
4.3.3.3.2 Resulting setup
1. Navigate to
Contextual help>>>Protection>>>Shutdown on power outagepage and to the When utility comes backsection.
2. Enable the "Keep shutdown sequence running until the end and then restart (forced reboot)".
3. Enable the "Automatically restart the UPS when battery capacity exceeds" and set it to 0%.
The storage will restart first, right after utility recovery without waiting the battery capacity to exceed a % limit.
4. Set Then Group 1 after to 120s.
The database servers will restart 120s after the utility recovery.
5. Set Then Group 2 after to 60s.
The database servers will restart 180s after the utility recovery.
4.4 Checking the current firmware version of the Network Module
Currentfirmware of the Network Module can be accessed in :
The Card menu :
Contextual help>>>Maintenance>>>System information>>>Firmware information: Firmware version x.xx.x
The Card menu : Contextual help>>>Maintenance>>>Firmware: Active FW version x.xx.x
4.5 Accessing to the latest Network Module firmware/driver/script
Download the latest Eaton Network Module firmware, driver or script from theEatonwebsitewww.eaton.com/downloads
When utility recovers, primary starts immediately.