Tripp Lite EVMAGU23X NEW Eaton G4 Universal-Input Managed PDU, 208V and 415/240V, 42 Outlets, Input Cable Sold Separately, 72-Inch 0U Vertical

Eaton G4 Gigabit Network Module GNM Firmware User Guide - Page 192

For EVMAGU23X NEW.

PDF File Manual, 231 pages, Read Online | Download pdf file

EVMAGU23X NEW photo
Loading ...
Loading ...
Loading ...
List of event codes
Information – 192
635CriticalBattery temperature low criticalBatterytemperature OKCheck battery
637CriticalBatterytemperature high criticalBattery temperature OKCheck battery
63ECriticalBattery faultBattery OKCheck battery
704CriticalInverter internal failureUPS OKService required
705CriticalInverter overloadNo power overloadReduce output load
706CriticalTemperature alarmTemperature OKCheck air conditioner
70BCriticalInverter short circuitEnd of inverter short circuitService required
805CriticalOutput short circuitOutput OKReduce output load
811CriticalParallel negative powerParallel power OKReduce output load
815CriticalCalibration faultCalibration OKService required
81ECriticalLoad unprotectedLoad protected-
7.5.2.2 Warning
CodeSeverityActive messageNon-active messageAdvice
001WarningOn batteryNo more on battery-
007WarningFan faultFan OKService required
00BWarningParallel UPS redundancy lostParallel UPS redundancy OKReduce output load
00EWarningParallel UPS communication lostParallel UPS communication OKService required
00FWarningParallel UPS not compatibleParallel UPS compatibility OKService required
010WarningUPS power supply faultUPS power supply OKService required
011WarningParallel UPS protection lostParallel UPS protection OKReduce output load
012WarningParallel UPS measure inconsistentParallel UPS measure OKService required
103WarningUtility breaker openUtility breaker closed-
104WarningInput AC frequency out of rangeInput AC frequency in range-
106WarningInput AC not presentInput AC present-
107WarningInput bad wiringInput wiring OKCheck input wiring
108WarningInput AC voltage out of range (-)Input AC voltage in range-
109WarningInput AC voltage out of range (+)Input AC voltage in range-
110WarningBuilding alarm (through dry
contact)
Building alarm OK-
11FWarningBuilding alarm (through Network
module)
Building alarm OK-
Loading ...
Loading ...
Loading ...