Powering down/up applications (examples)
Servicing the Network Management Module – 136
4.3.2.2.2 Resulting setup
UPS provides outlets (Group 1 and Group 2) and a primary output.
Connections can be done as described below:
Group 2: non-priority equipment
Group 1: critical equipment
Primary:criticalequipment
4.3.2.3 Step 2: Agent settings
4.3.2.3.1 Objective
Ensure IT solution is shutdown gracefully.
4.3.2.3.2 Resulting setup
1. InstallIPPSoftware on each server (Application, Database servers, Storage) and register the UPS load segment as power source:
Critical equipment:Group 1
Non-priority equipment:Group 2
Critical equipment: Entire UPS
2. Pair agent to the Network Module (
Pairing agent to the Network Module).
When done, each server appears in the Agent list.
3.Navigate toContextual help>>>Protection>>>Agent shutdown sequencingpage
4. Set the OS shutdown duration to the time needed for your server to shutdown gracefully.
This will make sureIPPshutdowns your servers before the load segment is powered down.
As a result, it will define the overall shutdown sequence duration for each load segments.
4.3.2.4 Step 3: Power outage policy settings
4.3.2.4.1 Objective
Use load segment policies to define shutdown sequencing.
4.3.2.4.2 Resulting setup
1. Navigate to
Contextual help>>>Protection>>>Shutdown on power outagepage on the Network Module
2. Set Primary and Group 1 to:
Customand set it to end shutdown sequence 180s before the end of backup time.
When primary shuts OFF, both group 1 and group 2 shut OFF immediately.
For examples of Agent settings, see the Agents shutdown sequencing sections.
For examples of Power outage policy, see the following sections:
Maximize availability policy example
Immediate graceful shutdown policy example
Load shedding policy examples
Custom policy examples