List of event codes
Information – 195
819WarningOutput voltage too highOutput voltage OKService required
81AWarningOutput voltage too lowOutput voltage OKService required
81BWarningUPS Shutoff requestedEnd of UPS shutoff requestedService required
81DWarningLoad not poweredLoad protected-
900WarningMaintenance bypassNot on maintenance bypass-
901WarningMaintenance bypass breaker
closed
Maintenance bypass breaker open-
B01WarningBatteries are aging. Consider
replacement
Batteries aging condition cleared-
7.5.2.3 Info
CodeSeverityActive messageNon-active messageAdvice
005InfoCommunication lost (with UPS)Communication recovered (with
UPS)
Service required
009InfoOn high efficiency / On ESS modeHigh efficiency disabled / ESS
disabled
-
013InfoUpgrading: limited communicationEnd of upgrade mode-
101InfoOn AVR (Boost)End of AVR (Boost)-
102InfoOn AVR (Buck)End of AVR (Buck)-
603InfoBattery dischargingEnd of UPS battery discharge-
63CInfoBattery informationBattery OK-
A00InfoGroup 1 is OFFGroup 1 is ON-
A01InfoGroup 2 is OFFGroup 2 is ON-
A0FInfoGroup is OFFGroup is ON-
7.5.2.4 Good
CodeSeverityActive message
60EGoodUPS external battery set as “No battery”
826GoodLoad powered
Alarms with a severity set as Good are not taken into account into the counter of active alarms.