Tripp Lite EVMAGU23X NEW Eaton G4 Universal-Input Managed PDU, 208V and 415/240V, 42 Outlets, Input Cable Sold Separately, 72-Inch 0U Vertical

Eaton G4 Gigabit Network Module GNM Firmware User Guide - Page 204

For EVMAGU23X NEW.

PDF File Manual, 231 pages, Read Online | Download pdf file

EVMAGU23X NEW photo
Loading ...
Loading ...
Loading ...
SNMP traps
Information – 204
7.5.6.2.2 Communication
CodeSeverityActive messageNon-active messageAdvice
1300InfoCommunication: No device connectedCommunication: Communication with the device is back-
1301InfoCommunication: Device not supportedCommunication: Communication with the device is back-
7.5.6.2.3 Alarms
CodeSeverityActive messageNon-active messageAdvice
1302InfoAlarms: the number of alarms is
high and above 5 000
Alarms: the number of alarms is
back to normal
It is recommended to
Export and Clear the alarm
log.
7.6 SNMP traps
7.6.1 UPS Mib
7.6.1.1 IETF Mib-2 Ups traps
This information is for reference only.
Trap oid :
.1.3.6.1.2.1.33.2.0.x
Description :
.1.3.6.1.2.1.33.2.0.1Sent whenever the UPS transfers on battery,
then sent every minutes until the UPS Comes back to AC Input.
.1.3.6.1.2.1.33.2.0.3Sent whenever an alarm appears.
The matching alarm oid is added as bound variables in the table below.
.1.3.6.1.2.1.33.2.0.4Sent whenever an alarm disappears.
The matching alarm oid is added as bound variables in the table below.
Alarm oid at :
.1.3.6.1.2.1.33.1.6.3.x
Description when trap 3Description when trap 4
.1.3.6.1.2.1.33.1.6.3.1Battery test failedBattery test OK
.1.3.6.1.2.1.33.1.6.3.2Battery dischargingEnd of UPS battery discharge
.1.3.6.1.2.1.33.1.6.3.3Low batteryBattery OK
.1.3.6.1.2.1.33.1.6.3.5Temperature alarmTemperature OK
.1.3.6.1.2.1.33.1.6.3.6Input AC not presentInput AC present