Loading ...
Loading ...
Loading ...
![](https://manualsfile.com/fullContents/37153897-evmagu23x-new/bg2a.png)
Protection
Contextual help of the web interface – 42
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Software is not able to communicate with the Network module
Symptoms
In the Network Module,in
Contextual help>>>Protection>>>Agent list>>>Agent list table , agent is showing "Lost" as
a status.
In the Network Module,in Contextual help>>>Settings>>>Certificate>>>Trusted remote certificates , the status of
theProtected applications (MQTT) is showing"Not valid yet".
IPP/IPM shows "The authentication has failed", "The notifications reception encountered error".
Possible cause
The IPP/IPM certificate is not yet valid for the Network Module.
Certificates of IPP/IPM and the Network Module are not matching so that authentication and encryption of connections
between the Network Module and the shutdown agents is not working.
Setup
IPP/IPM is started.
Network module is connected to the UPS and to the network.
Action #1
Check if the IPP/IPM certificate validity for the Network Module.
STEP 1:Connect to the Network Module
On a network computer, launch a supported web browser. The browser window appears.
In the Address/Location field, enter:https://xxx.xxx.xxx.xxx/where xxx.xxx.xxx.xxx is the static IP address of the
Network Module.
The log in screen appears.
Enter the user name in the User Name field.
Enter the password in the Password field.
ClickLogin. The Network Module web interface appears.
STEP 2:Navigate toSettings/Certificatespage
STEP 3:In theTrusted remote certificatessection, check the status of theProtected applications (MQTT).
If it is "Valid"go to Action#2 STEP 2, if it is "Not yet valid", time of the need to be synchronized with IPP/IPM .
STEP 4:Synchronize the time of the Network Module with IPP/IPM and check that the status of theProtected applications
(MQTT)is now valid.
Communication will then recover, if notgo to Action#2 STEP 2.
Action #2
Pair agent to the Network Module with automatic acceptance (recommended in case the installation is done in a secure and
trusted network).
STEP 1:Connect to the Network Module.
On a network computer, launch a supported web browser. The browser window appears.
In the Address/Location field, enter:https://xxx.xxx.xxx.xxx/where xxx.xxx.xxx.xxx is the static IP address of the
Network Module.
The log in screen appears.
Enter the user name in the User Name field.
Enter the password in the Password field.
Click
Login. The Network Module web interface appears.
For manual pairing (maximum security), go to Servicing the Network Management Module
>>>Pairing agent
to the Network Module
section and then go to STEP 2, item 1.
Loading ...
Loading ...
Loading ...