EMP detection fails at discovery stage
Troubleshooting – 226
8.3.3 Action
In the server system BIOS, change the setting for Automatic Power ON to "Enabled".
8.4 EMP detection fails at discovery stage
In the Network Module,in
Contextual help>>>Environment>>>Commissioning/Status, EMPs are missing in the Sensor
commissioning table.
8.4.1 Symptom #1
The EMPs green RJ45 LED (FROM DEVICE) is not ON.
8.4.1.1 Possible causes
The EMPs are not powered by the Network module.
8.4.1.2 Action #1-1
Launch again the discovery, if it is still not ok, go to Action #1-2.
8.4.1.3 Action #1-2
1- Check the EMPs connection and cables.
Refer to the sectionsServicing the EMP>>>Installing the EMP>>>Cabling the first EMP to the deviceandServicing the
EMP>>>Installing the EMP>>>Daisy chaining 3 EMPs.
2- Disconnect and reconnect the USB to RS485 cable.
3- Launch the discovery, if it is still not ok, go to Action #1-3.
8.4.1.4 Action #1-3
1- Reboot the Network module.
2- Launch the discovery.
8.4.2 Symptom #2
The EMPs orange RJ45 LEDs are not blinking.
8.4.2.1 Possible causes
C#1: the EMP address switches are all set to 0.
C#2: the EMPs are daisy chained, the Modbus address is the same on the missing EMPs.
8.4.2.2 Action #2-1
1- Change the address of the EMPs to have different address and avoid all switches to 0.
Refer to the sectionServicing the EMP>>>Defining EMPs address and termination>>>Manual addressing.
2- Disconnect and reconnect the USB to RS485 cable. The address change is only taken into account after an EMP power-up.
3- Launch the discovery,if it is still not ok, go to Action #2-2.
8.4.2.3 Action #2-2
1- Reboot the Network module.