4. Telnet/SSH Console
4.2.3.3 RADIUS Servers
This is the section of the menu used to define the RADIUS Servers. There is a maximum of 2 RADIUS Servers that can be defined. If a slot is
available to create another server, the address value will be “Server Not Defined”.
Radius Servers Summary Menu
-------- Radius Servers Menu ---------------------------------------------------
-----------------------------------------------------------------------------
# | Address | Priority | AUTH PORT | ACCT PORT
-----------------------------------------------------------------------------
1 10.0.0.11 1 1812 1813
2 Server Not Defined
#- Radius Server
X- Security Menu
M- Return to Main Menu
<ENTER> Refresh Menu
>> 1
Radius Server Detail Menu
-------- Radius Server Detail Menu ---------------------------------------------
Address : 10.0.0.11
Priority : 1
Shared Secret : tripplite
Authentication Port : 1812
Accounting Port : 1813
1- Address
2- Priority
3- Shared Secret
4- Authentication Port
5- Accounting Port
A- Apply Changes
C- Delete Radius Host
X- Radius Servers Menu
M- Return to Main Menu
<ENTER> Refresh Menu
>> x
-------- Radius Servers Menu ---------------------------------------------------
-----------------------------------------------------------------------------
# | Address | Priority | AUTH PORT | ACCT PORT
-----------------------------------------------------------------------------
1 10.0.0.11 1 1812 1813
2 Server Not Defined
#- Radius Server
X- Security Menu
M- Return to Main Menu
<ENTER> Refresh Menu
Menu Data
localadmin
This is the administrator account and has Read/Write access to all program
areas. This user cannot be deleted or its facility access permission be
modified, but the username and password may be changed from its default
settings. The default password is same as the username.
localmanager
This account has default access as Read/Write to all areas except to
the security area of the program. The default password is same as the
username.
localguest
This account has read-only access to Device Status, Logging, and Info
areas of the program. The default password is same as the username.
public
This account is not a program user. It is an SNMPv1 Read-Only
community.
tripplite
This account is not a program user. It is an SNMPv2c Read/Write
community. This the default community string that Tripp Lite’s
PowerAlert Network Shutdown Agent uses to discover Tripp Lite SNMP
devices on the network.
Users 6-12 are not defined.