8. Appendix
Sample A
Sample 'dictionary.tripplite' FreeRadius Configuration File
##############################################################################
VENDOR TrippLite 850
BEGIN-VENDOR TrippLite
#
# Access is granted to the various facilities within the PowerAlert software
# by means of the TrippLite-Authorization attribute, which is a comma-delimited
# string of facility-code to access-level pairs.
#
# Facility Codes: default, security, networksettings, systemsettings, systreminfo,
# logging, devicestatus, devicecontrols, deviceevents,
# deviceloads, actions, schedules, discovery
#
# Access Levels: none (or 0), ro (or 1), rw (or 2)
#
# Example: default=rw,security=none,systemsettings=ro
#
# - The default access for all non-specified facilitys is read/write
# - The user has no access to the security facility
# - The user has read-only access to the system settings
#
ATTRIBUTE TrippLite-Authorization 1 string
#
# Comma-delimited string of outlet security realms from 1 through 32 to which
# an otherwise restricted user has read-write access.
#
# Example: 1-5,10,15
#
# - User has read-write access to realms 1, 2, 3, 4 and 5
# - User has read-write access to realms 10 and 15
#
ATTRIBUTE TrippLite-Outlet-Realms 2 string
#
# Simple message, usually sent as part of accounting
#
ATTRIBUTE TrippLite-Message 3 string
END-VENDOR TrippLite