5
When used with a Tripp Lite UPS during a power failure, WEBCARDLX is pre-configured to shut down the UPS system two minutes after receiving a
low battery signal. This allows the UPS system to provide the maximum available runtime to connected equipment. To change the default setting,
select Device Shutdown from the Action Type dropdown menu (refer to 3.4.4 Configurations/Actions or 4.2.2.1 Action Profiles for Telnet/SSH).
2.3 Default UPS System Shutdown Settings
2. Initial Configuration
LX Platform devices function as SNMP-managed devices on your network, using the SNMP agent and Management Information Base (MIB). The
SNMP agent resides in the LX Platform device firmware and responds to standard SNMP commands (Get, Get Next and Set). It can also generate
SNMP traps (messages). The MIB determines which parameters can be monitored and controlled. Three MIB files—TRIPPLITE.MIB,
TRIPPLITE-PRODUCTS.MIB and RFC-1628-UPS.MIB—must be loaded on each Network Management Station that will monitor the managed
device. (The files can be downloaded from www.tripplite.com/support. Consult your Network Management Station software documentation for
instructions on how to import MIB files.)
Note: SNMP Users are configured in the Configuration > Security > User section of PADM.
SNMPv3 Definitions
Username The identifier of the user profile. SNMPv3 maps Gets, Sets and Traps to a user profile by matching the username
of the profile to the username in the data packet being transmitted. A username can have up to 32 ASCII
characters (alphanumeric and the following special characters: !@#$%^*(){[}]~_-).
Authentication Passphrase A phrase of 8 to 32 ASCII characters (alphanumeric and the following special characters: !@#$%^*(){[}]~_-)
that verifies that the Network Management System (NMS) communicating with this device through SNMPv3 is
the NMS it claims to be, that the message has not been changed during transmission, and that the message
was communicated in a timely manner, indicating that it was not delayed and that it was not copied and sent
again later at an inappropriate time.
Privacy Passphrase A phrase of 8 to 32 ASCII characters (alphanumeric and the following special characters: !@#$%^*(){[}]~_-)
that ensures the privacy of the data (by means of encryption) that a Network Management System (NMS) is
sending to this device or receiving from this device through SNMPv3.
Authentication Protocol The Tripp Lite implementation of SNMPv3 supports only SHA (as of 15.04.0) authentication.
Privacy Protocol The Tripp Lite implementation of SNMPv3 supports only AES (as of 15.04.0) as the protocol for encrypting and
decrypting data.
Public Value A field provided to enter a username/password hint for SNMPv3 Admin users. This SNMPv3 value is part of the
SNMPv3 USM User Table.
2.4 SNMP Configuration
C. When the login prompt appears, enter localadmin for both the login and password. From the main menu, navigate to the Static IP settings
menu using the following sequence:
3: Network Configuration
1: IP Configuration
3 or 4: IPv4 or IPv6 settings
1: Method
2: Static
D. Assign the Address, Subnet Mask, Gateway, Primary DNS, etc.
E. Save your settings by selecting "A" (apply).
F. For the settings to take effect, select “Y” to Restart PowerAlert Now.
G. Close the terminal session.
Note: User names and passwords are case sensitive.
2.2 Saving Configuration Changes
Most configuration changes made in PowerAlert Device Manager will take effect immediately. PADM and Telnet/SSH will typically advise you if your
configuration changes require a restart to take effect.
Regardless, to ensure that configuration changes persist, it is recommended that you restart PowerAlert Device Manager. Most configuration
changes will auto-save after about 30 minutes of idle time; changes to the network settings will not.
Restarting PADM will not disrupt power to equipment powered through your UPS or PDU and has no effect on the general operation of your
Tripp Lite device.