LARGE CASSETTE TECHNICAL OVERVIEW
E-10
ENGLISH
Topic Title
DIP Switch Settings
Description
Capacity Room Card Running Mode Unit Type
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8
Capacity: 24kBTU(7.1kW) ON ON OFF --- --- --- --- ---
Capacity: 30kBTU(9.0kW) OFF OFF ON --- --- --- --- ---
Capacity: 35kBTU(10.5kW) ON OFF ON --- --- --- --- ---
Capacity: 42kBTU(12.5kW) OFF ON ON --- --- --- --- ---
Capacity: 48kBTU(14.0kW_ ON ON ON --- --- --- --- ---
Room card invalid(default) --- --- --- OFF --- --- --- ---
Room card valid --- --- --- ON --- --- --- ---
Heat pump(default) --- --- --- --- OFF --- --- ---
Cooling only --- --- --- --- ON --- --- ---
High performance cassette --- --- --- --- --- OFF OFF ON
Indoor unit Address
(Indoor unit address for one wired
controller control more than one unit)
BM3-5 BM3-6 BM3-7 BM3-8
0 (master) OFF OFF OFF OFF
1 (slave) OFF OFF OFF ON
2 (slave) OFF OFF ON OFF
3 (slave) OFF OFF ON ON
4 (slave) OFF ON OFF OFF
5 (slave) OFF ON OFF ON
6 (slave) OFF ON ON OFF
7 (slave) OFF ON ON ON
8 (slave) ON OFF OFF OFF
9 (slave) ON OFF OFF ON
10 (slave) ON OFF ON OFF
11 (slave) ON OFF ON ON
12 (slave) ON ON OFF OFF
13 (slave) ON ON OFF ON
14 (slave) ON ON ON OFF
15 (slave) ON ON ON ON
BM1 DIP Switch Settings
Wired Controller Communication Address