OUTDOOR TECHNICAL OVERVIEW
B-22
ENGLISH
Topic Title
DIP Switch Settings
Description SW5-1 SW5-2 SW5-3 SW5-4 SW5-5 SW5-6 SW5-7 SW5-8
Heat pump OFF* ---- ---- ---- ---- ---- ---- ----
Cooling only ON ---- ---- ---- ---- ---- ---- ----
Defrost temp. selection (used for mild weather
defrost)
---- OFF* ---- ---- ---- ---- ---- ----
Defrost temp. selection (used for severe weather
defrost)
---- ON ---- ---- ---- ---- ---- ----
Power input restrict
invalid ---- ---- OFF* ---- ---- ---- ---- ----
Power input restrict valid ---- ---- ON ---- ---- ---- ---- ----
2U20EH2VHA ---- ---- ---- OFF ON ON ---- ----
3U24EH2VHA ---- ---- ---- ON ON OFF ---- ----
Factory use only ---- ---- ---- ---- ---- ---- OFF* ----
Factory use only ---- ---- ---- ---- ---- ---- ON ----
Quiet operation valid ---- ---- ---- ---- ---- ---- ---- OFF*
Quiet operation invalid ---- ---- ---- ---- ---- ---- ---- ON
Note:
1. Power input restrict selection: OFF-invalid; ON-valid(≤3500W)
2. Quiet operation: If OFF, the outdoor unit will calculate and obtain the average ambient temperature of the unit within the
last 24 hours, Tao_average_24. Then compare the current ambient temperature with the ambient temperature average
Tao_average_24, and combine it with the previous ambient temperature trend to determine whether it can enter Quiet
operation (low compressor speed and low O.D. fan speed).
SW5 SW7SW6
SW5 DIP Switch Settings
*Factory Default Setting
WJ26X25053 - Outdoor Power Control Board DIP Switch Settings