TROUBLESHOOTING & REFERENCES
J-27
ENGLISH
Topic Title
Flow Charts
Reconnect
Power off. Is pressure switch
wiring connection ok?
Use multimeter to check the high
pressure switch. Is the switch
short circuited?
Is the EEV coil wiring correct and
firmly in place?
Is the stop valve is open?
Use a multimeter to check
the resistance of Tc & Tm.
Are they withing range?
Is the piping system is
clogged?
Is the connection pipe is bent?
The pressure is bad,
replace it.
Open the stop valve
Clean the piping system
Replace the connection
pipe
Replace the
sensor
Ye s
Ye s
No
Ye s
Ye s
No
No
No
No
No
Ye s
No
No
Reconnect the EEV
coil wiring
[44] High pressure detected in system
The minimum temperature value of indoor pipe Tm
and outdoor Ts is lower than -45 °C during cooling
mode, or minimum temperature value of outdoor Tc
and outdoor Te is lower than -45 °C.
Possible causes:
High pressure sensor detection value is incorrect
Refrigerant overcharge
Blocked liquid line piping
The outdoor unit cannot be turned on normally
due to failure to open outdoor heat exchanger
electronic expansion valve when heating.
The operation environment is beyond the allowed
range.
Power on
Short the low pressure
switch terminal on the PCB.
Does the system report a
failure?
Is the fan motor ok?
Is the resistance of Te and
Tc2 in range?
The PCB is bad,
replace it.
Replace
sensor
No
Ye s
Ye s
Ye s
No
No
Replace the fan
motor
[45] Low pressure detected in system
The minimum temperature value of indoor pipe Tm and
outdoor Ts is lower than -45 °C during cooling mode, or
minimum temperature value of outdoor Tc and outdoor Te is
lower than -45 °C.
Possible causes:
Low pressure sensor detection value is incorrect
Low refrigerant charge
System air leakage
Blocked low pressure or liquid line piping
The outdoor unit cannot be turned on normally due to failure
to open outdoor heat exchanger electronic expansion valve
when heating.
The operation environment is beyond the allowed range.