TROUBLESHOOTING & REFERENCES
J-24
ENGLISH
Topic Title
Flow Charts
[16] Lack of refrigerant or discharging pipe blocked
Discharge & suction temperature Td-Ts≥80°C 10 minutes
after compressor start. Error status locks if it occurs 3 times
in 1 hour.
Possible causes:
Wrong sensor connection
Lack of refrigerant
The senor is bad
The 4-way valve is bad
The electronic expansion valve is bad
Out of the operating range
Correct wiring
Is the sensor wiring correct
and firmly connected?
Is the system leaking, or
lacking refrigerant?
Is the resistance of the
Td and the Tcm sensors
within range?
Repair leak and recharge
refrigerant
Replace the
sensor
Ye s
No
Ye s
No
Use the unit according to
the allowable operating
range of the unit.
Ye s
Is there an Internal
leakage in the 4-way
valve?
No
Replace 4-way
valve
Ye s
No
Adjust the valve opening
Ye s
Is the electronic
expansion valve over
throttled?
[17] 4-way valve reversing failure
Indoor pipe & indoor ambient temperature Tm-Tai≥5°C
10 minutes after compressor started. Error status locks
if it occurs 3 times in 1 hour.
Possible causes:
The 4-way valve is bad
The PCB is bad
The 4-way valve coil connection is bad
The system pressure dierence is too small.
Reconnect
Is connection between the
4-way valve and PCB is good?
Is the 4-way valve coil
wiring firmly in place and
characteristics correct?
Is the system meeting
4-way valve reversing
conditions (Pd-
Ps>0.6Mpa)?
Is there air noise after 4-way
valve reverses, and the temp.
of connection pipes on 4-way
valve normal?
Correct wiring or replace
Check if the
compressor is running
Replace
PCB
Replace 4-way
valve
Ye s
Ye s
Ye s
No
Ye s
No
No
Ye s
No
Is 208/230VAC Measured on
PVB CN5 PCB after 4-way
valve reversing conditons are
met?