709/709H/710
Users Manual
34
While logging, the screen in Figure 50 shows to monitor
progress.
Figure 50. Active Logging Screen
8. Push
to stop logging and go to the first data log screen.
The data items are:
The top line indicates is logging is in progress (Logging) or is
stopped (Stopped). Logging stops automatically when storage
is full or before the Product is turned off when the battery
reaches its low voltage automatic shutoff limit of 5.6 V.
Interval is the item previously selected.
Elapsed is the time since the log was started, updated each
time a new sample is saved.
Records used is the total number used to date for all sessions,
updated each time a new sample is saved.
Records free is the total number that remain unused, updated
each time a new sample is saved.
709H is the present measurement, updated as often as
possible.
PV mA is the last HART device measurement, updated as
often as possible.
Valve Tests (710)
The 710 adds specialty tests to the basic HART functionality of the
709H to perform tests on HART smart valve positioners.
1. Connect to the control valve.
2. Push
.
3. Turn the selection knob to move the highlight to HART Comm
menu and push the selection knob to select.
4. Push the selection knob to select the option.
5. Rotate the selection knob to highlight mA Src. - HART Valve
and push the knob to make the selection.
6. Select HART CONNECT to initiate HART polling for
connected HART devices.
7. When the 710 finds a device, push the selection knob to
select.
8. From the HART Valve operation screen, select Valve Tests.
See available options for valve tests in Figure 51.
Figure 51. Valve Tests