709/709H/710
Users Manual
26
Write URV
The Product warns you to change the loop to MANUAL before you
proceed. Push the selection knob to proceed. Push
to go to
the LRV and URV menu.
The present URV value and units show. See Figure 34.
Figure 34. Write URV Screen
1. Push the selection knob to move the decade cursor.
2. Turn the selection knob to increment or decrement the value
in steps indicated by the selected decade.
3. Push and hold the knob to send the new value to the HART
device, remaining on this display. An error shows if the HART
device rejects the value.
4. Push
to go to the LRV and URV menu. A prompt to
change the loop to AUTOMATIC shows first.
Write PV Unit
The Product warns you to change the loop to MANUAL before you
proceed. Push the selection knob to proceed. Push
to go to
the Modify Setup menu.
The available units show with the present unit. For example, if the
present unit is PSI, a list of pressure units show. Another example
is if the present unit is °C, a list of temperature units show.
PV Units settings are limited to the common practice command
specification for HART protocol. Support for non-standard PV units
is limited if proprietary to a manufacturer that uses device-specific
commands. See Figure 35.
Figure 35. Write PV Unit Screen
The tag name is truncated if too long to fit on one line. The
symbol in the upper right corner flashes to show a working HART
connection.
To write a new value:
1. Rotate the selection knob to move the highlight
2. Push and hold the selection knob to send the new value to the
HART device.
The screen prompts you to change the loop to AUTOMATIC
and changes to the Modify Setup menu.
An error message shows if the HART device rejects the value
for any reason.