Note: A message text can be sent with Email, SMS and Nagios actions. This configurable message can include selected values:
$AR_TRIGGER_VAL = the trigger value for the check e.g. for UPS Status, it could be onbatt or battlow
$AR_VAL = the value returned by the check e.g. for ups status, it could be online/onbatt/battlow
$AR_CHECK_DEV = the device name of the device being checked e.g. for Alarm, the alarm name
$TIMESTAMP = the current timestamp
$HOSTNAME = the hostname of the console server
The default message text is: $TIMESTAMP: This action was run - Check details: value $AR_VAL vs trigger value $AR_TRIGGER_VAL.
7.3.1 Send Email
Click on Send Email as the Add Trigger Action. Enter a unique Action Name and set the Action Delay Time
Specify the Recipient Email Address for whom to send this email and the Subject of the email. For multiple recipients, you
can enter comma-separated addresses.
Edit the Email Text message to send. Click Save New Action.
Note: An SMS alert can also be sent via an SMTP (email) gateway. You will need to specify the Recipient Email Address in the format
specified by the gateway provider (e.g,. for T-Mobile it is [email protected]).
7.3.2 Send SMS
Click on Send SMS as the Add Trigger Action. Enter a unique Action Name and set the Action Delay Time.
Specify the Phone number that the SMS will be sent to in international format (without the +).
Edit the Message Text to send and click Save New Action.
Note: The SMS alert can only be sent if there is an internal cellular modem attached. However, an SMS alert can also be sent via SMTP
SMS gateway, as described above.
7.3.3 Perform RPC Action
Click on Perform RPC Action as the Add Trigger Action. Enter a unique Action Name and set the Action Delay Time
Select a power Outlet and specify the Action to be performed (power ON, OFF or Cycle).
Click Save New Action.
7.3.4 Run Custom Script
Click on Run Custom Script as the Add Trigger Action. Enter a unique Action Name, and set the Action Delay Time.
Create a script file to execute when this action is triggered and enter the Script Executable file name (e.g., /etc/config/
action.sh).
Set the Script Timeout (the maximum run-time for the script). Leave as 0 for unlimited.
Enter any Arguments that are to be passed to the script and click Save New Action.
7.3.5 Send SNMP Trap
Click on Send SNMP Trap as the Add Trigger Action. Enter a unique Action Name, and set the Action Delay Time.
Note: SNMP Trap actions are valid for Serial, Environmental, UPS and Cellular data triggers.