City Series CC40E-11 | 57
installation
Venting Arrangement for Vertical Terminations - Straight Vertical Venting and/or with a Max. of Two (2) 90
o
Elbows (1 - 90
o
= 2 - 45
o
)
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using two
90
o
elbows, with Rigid Pipe Venting Systems.
Two 45
o
elbows equal to one 90
o
elbow.
Vent must be supported at offsets.
Minimum distance between elbows is 1 ft. (305mm).
Maintain clearances to combustibles as listed in the
"Clearances" section.
Horizontal vent must be supported every 3 feet.
Firestops are required at each floor level and whenever
passing through a wall.
Must use optional rigid pipe adaptor (Part# 510-994) when
using rigid pipe vent systems.
Refer to the "Vent Restrictor Position" section for details on
how to change the vent restrictor from the factory setting
of Set 0 through to Set 3 if required.
Maximum: 37 ft. (11.2m)
Minimum
8’6” (2.6m)
Min. 56-1/4”
(1429mm)
*Minimum length of pipe
between elbows 12” (305mm)
Maximum: 27 ft. (8.2m)
0
0
2
2
4
4
6
6
4
4
0
0
8
8
1
1
0
0
1
1
2
2
1
1
4
4
1
1
6
6
1
1
8
8
2
2
0
0
2
2
2
2
2
2
4
4
2
2
6
6
2
2
8
8
3
3
0
0
Vertical Height (Feet)
3
3
2
2
3
3
4
4
3
3
6
6
3
3
8
8
6
6
8
8
Horizontal (Feet)
2
2
0
0
4
4
1
1
0
0
1
1
2
2
1
1
6
6
1
1
8
8
1
1
4
4
2
200
Vent Restrictor on Set 2
Vent Restrictor on Set 3
Vent Restrictor on Set 1
*