Electrical Connections
Consult the installation drawing supplied with the walk-in to determine which application is required. Unless otherwise
shown, the door section is furnished with a factory installed vapor proof light fixture on the interior of the section, and a
light switch with pilot light indicator flush mounted on the exterior. All freezer door sections and cooler doors with metal
thresholds are equipped with anti-condensate heaters around the entire perimeter. Heaters run underneath the
thresholds, so care must be used if drilling through so that the wire does not get damaged.
All wiring in the door and door section for heaters, switch, and light fixtures is factory installed and requires only simple field
connection for complete operation; typical service required is 120-volt, 60 cycle, single phase, unless otherwise shown
(consult the installation drawing).
Electrical connections for the anti-condensate heaters are made on the interior of the door section inside the fixture base of
the vapor proof light. Consult the assembly drawing for the specific electrical connection point for your unit.
CAUTION
Force sealant around wires in entrance conduit to prevent moisture from entering fixture. Failure to
eliminate airflow in conduit could void warranty.
For wiring diagrams, visit our website or scan the QR Code below.