Kolpak P7-0806-CT Walk-In Cooler & Top Mounted Compressor

Walk in installation - Page 12

For P7-0806-CT.

PDF File Manual, 40 pages, Read Online | Download pdf file

P7-0806-CT photo
Loading ...
Loading ...
Loading ...
12
Apply two beads of non-drying butyl sealant to the bottom side of the screeds.
Start at back corner and fasten screeds in place for two adjoining walls. Fasten screed as shown on assembly drawing with
fasteners provided.
Each section of screed is to have a minimum of two fasteners, one on each end. This is especially true for screed sections
under the door. For long screed sections, fasteners should be spaced at a maximum of four feet.
To insure proper fit, do not fasten screeds for remaining walls until the first two walls are assembled.
CAUTION
Thermal breaks are required in freezer applications and recommended in cooler applications to separate
the interior flooring from the exterior floor. Thermal breaks prevent heat transfer and increase energy
efficiency.
A 3/8” bead of non-drying butyl sealant is required and should be continuous around the complete
perimeter of the walk-in. This sealant application will assist in maintaining the vapor barrier.