Tripp Lite PDU3EVSR1L2130 NEW series 8.6kW 200-240V 3-Phase IsoBreaker Managed PDU - Gigabit, 36 Outlets, L21-30P Input, LCD, 10 ft. 3 m Cord, 0U, 70 in. 1.8 m Height, TAA

Owner's Manual 3-Phase Monitored & Switched 0U PDUs Multi-Language - Page 22

For PDU3EVSR1L2130 NEW.

PDF File Manual, 200 pages, Read Online | Download pdf file

PDU3EVSR1L2130 NEW photo
Loading ...
Loading ...
Loading ...
22
LCD Screen
Settings g Iso Breaker
The Iso Breaker detects a bank overcurrent condition and takes quick action
to turn off selective outlets before the bank breaker trips, thus preventing
the bank circuit-breaker taking down all the outlets in the bank.
Iso Breaker is the 5th item in the Settings submenu. It allows enable/
disable configuration of the Iso Breaker feature.
Settings g SNMP Reset (Remote Reset)
SNMP Reset (Remote Reset) is the 6th item in the Settings submenu.
Resetting the SNMP Card module will not erase network settings or
interrupt AC power.
Note: If the unit is set to DHCP, it may receive a new IP Address from the server
which is different than the one provided before.