FLUKE 1760 TR US Three-Phase Power Quality Recorder with Trans Topas

User Manual for the Fluke 1760 TR US Three-Phase Power Quality Recorder with Trans Topas - Page 90

For 1760 TR US.

PDF File Manual, 93 pages, Read Online | Download pdf file

1760 TR US photo
Loading ...
Loading ...
Loading ...
Options and Accessories
Accessories 6
6-25
Temperature coefficient: 0.005 % of range/ °C
Safety: 600 V CAT IV, type B sensor, pollution
degree 2
General Characteristics
Cable length: 4 m (156 inches)
Length of measuring head: 91 cm (36 inches)
Operating temperature range: 10 °C - +70 °C
Storage temperature range: 20 °C - +90 °C
Operating humidity: 10 % - 80 % (non condensing)
Weight: Approx. 400 g
Order-number: 2540492
Reference Conditions
Environment temperature range: +18 °C to +26 °C
Humidity: 20 – 75 %
Current: Nominal value In, sinusoidal waveform, 48 –
65 Hz
Distortion factor: <1 %. Stray field <40 A/m, conductor centered
within the Flexi current sensor
Safety Standards
IEC/EN 61010-1 2
nd
edition
IEC/EN 61010-2-032
IEC/EN 61010-031
EMC Standards
EN61326 –1:2006
Accuracy (Typical, for 50/60 Hz)
Linearity, error in % of measured value, primary current in A:
1.888.610.7664 sales@GlobalTestSupply.com