1760
Users Manual
1-10
Note
Channels ‘CH1’ to ‘CH4’ are labeled:
Schild CH1.wmf
The text TRANSIENT indicates that these channels can be equipped with a
fast transient option.
Channels ‘CH5’ to ‘CH8’ cannot be used for fast transient recordings and
are labeled like this:
schild ch5.wmf
Functional Description
A Mains Connector
Connect the device to 83 V – 264 V AC-47 Hz – 65 Hz or 100 V – 375 V DC, power
consumption approx. 30 W.
Note
Connect the supply cable of the device only to sections CAT I, II or III of
the supply system the voltage to earth may not exceed 300 V.
B Mains Switch
Activate the mains switch to switch the device on or off.
Note
The switch is secured by a mechanical feature against inadvertent
activation. Lift the knob slightly before moving it to the other position.
Instrument can be turned on only if the mains power supply is connected
and the supply voltage is within the specified range.
If the mains switch is in position I the instrument is turned on automatically
as soon as an appropriate supply voltage is applied to the mains connector.
If there is no mains supply and the battery pack capacity is too low the
instrument is turned off automatically.
Rebooting the Instrument
To reboot the instrument:
1. Set the mains switch to the 0-position.
2. Wait until all LEDs are off.
3. Connect instrument to mains and set the mains switch to the I-Position.