Options and Accessories
Accessories 6
6-11
Crest factor: < 3
Peak current: 18 A, 180 A
Max. non destructive current: Up to 200 A rms
Conductor position influence: < 0.5 % of range at 50/60 Hz
Error due to adjacent conductor: 15 mA/A at 50 Hz
Phase error (to reference conditions): < ±0.5 degrees
Frequency range (clamp without the
instrument):
40 Hz – 10 kHz (3 dB)
Temperature coefficient: 0.015 % of range/ °C
Safety: 300 V AC CAT IV, type C sensor, pollution
degree 2
General Characteristics
Maximum conductor size: Diameter: 15 mm.
Bus bar: 15 x 17 mm
Cable length: 2 m
Operating temperature range: 10 °C - +55 °C
Storage temperature range: 20 - +70 °C
Operating humidity: 15 % - 85 % (non-condensing)
Weight (per clamp): Approx. 220 g
Order-number: 2540461
Reference Conditions
Environment temperature range: +18 °C to +26 °C
Humidity: 20 to 75 % rh
Current: Sinusoidal waveform, with 48 to 65 Hz
Distortion factor: < 1 %, no DC component, stray field < 40 A/m,
conductor centered within the clamp jaws
Safety Standards
IEC/EN 61010-1 2
nd
edition
IEC/EN 61010-2-032
IEC/EN 61010-031
EMC Standards
EN61326 –1:2006
Accuracy (Typical, for 50/60 Hz)
Linearity, error in % of measured value, primary current in A:
1.888.610.7664 sales@GlobalTestSupply.com
Fluke-Direct.com