7. Communications
7.4 RS-232 Communication Port Denition
Notes:
• The USB, RS-232 and RS-485 interfaces cannot be used simultaneously. Only one interface can be used at a time.
• These three communication ports use a MODBUS protocol. Refer to the S3M10-20kVA 3-Phase MODBUS Owner’s Manual. The
MODUBS manual may be downloaded from the specic S3M10-20K UPS model page at Tripplite.Eaton.com.
The RS-232 port is a male connector.
Connection Between the Connected Computer’s RS-232 Port and UPS System’s RS-232 Port
Computer RS-232 Port UPS RS-232 Port
Pin 2 Pin 2 UPS send, PC receive
Pin 3 Pin 3 PC send, UPS receive
Pin 5 Pin 5 Ground
Available Functions of the RS-232 Port
Monitor UPS power status
Monitor UPS alarm data
Monitor UPS run parameters
Timing o/on setting
One-to-one communication, UPS to computer, at a distance less than 5 m
RS-232 communication data format
Baud rate: 9600 bps
Byte length: 8 bit
End bit: 1 bit
Parity check: None
7.5 RS-485 Communication Port Denition
Notes:
• The USB, RS-232 and RS-485 interfaces cannot be used simultaneously. Only one interface can be used at a time.
• These three communication ports use a MODBUS protocol. Refer to the S3M10-20kVA 3-Phase MODBUS Owner’s Manual. The
MODUBS manual may be downloaded from the specic S3M10-20K UPS model page at Tripplite.Eaton.com.
The RS-458 Port is a female connector.