4. Operation
4.1.3 Bypass Mode
If the inverter is out of order, or if overload occurs, the static transfer switch will activate to transfer the load from
the inverter supply to bypass supply without interruption to the critical load. In the event the inverter output is not
synchronized with the bypass AC source, the static switch will perform a transfer of the load from the inverter to the
bypass with power interruption to the critical AC load. This is to avoid paralleling of unsynchronized AC sources. This
interruption is programmable but typically set to be less than an electrical cycle, e.g. less than 15 ms (50 Hz) or less than
13.33 ms (60 Hz).
SINGLE INPUT: Mains Input DUAL INPUT: Mains Input and Bypass Input
Figure 4-3: Bypass Mode
4.1.4 ECO Mode
When the UPS is at AC Mode and the requirement to the load is not critical, the UPS can be set at ECO mode in order
to increase the eciency of the power supplied. At ECO mode, the UPS works at Line-Interactive mode, so the UPS will
transfer to bypass supply. When the AC is out of set window, the UPS will transfer from bypass to Inverter and supplies
power from the battery, and then the LCD shows all related information on the screen. The UPS will default to ECO
Mode after powering up.
Figure 4-4: ECO Mode
Maintenance Breaker
AC Input
AC Input
Bypass Input
Output
Output
Maintenance Breaker
Static Bypass
Rectier
Rectier
Battery Breaker
Battery Breaker
Inverter
Inverter
Output Breaker
Output Breaker
Bypass Breaker
Bypass Breaker
Battery Input
Battery Input
Input Breaker
Input Breaker
Static Bypass
Maintenance Breaker
AC Input
Output
ECO Mode
Static Bypass
Rectier
Battery Breaker
Inverter
Output Breaker
Bypass Breaker
Battery Input
Input Breaker
Bypass Mode
Loading ...
Loading ...
Loading ...