4. Operation
1. Click the Advanced Setup icon. Select the conguration to be changed/saved. Click the Back icon to return to the
previous window, or click the Home Page icon to jump to the main page.
Figure 4-24: Advanced Setup Interface
AdvancedSetupCongurations:
Working Mode - Select the work mode of UPS, work mode: Single mode, Parallel Mode, ECO mode.
Single Mode: Single UPS (not paralleled)
Parallel Mode: When in Parallel Mode for capacity, multiple UPS systems supply power to the load. When in Parallel
Mode for redundancy, multiple UPS systems are connected to supply redundant power.
ECO Mode (Initial Power-Up Default): Green mode & energy saving mode. The UPS will default to ECO Mode
after powering up.
Auto Turn-on: Select the UPS start logic, (Default) Enable: UPS start inverter output automatic, Disable: No output
Note: If you want the UPS to auto restart after the batteries reach a low voltage cut-o (LVC) and the UPS turns o, Auto Turn-on
MUST be set to Enable.
Operation Mode - Select the Operation Mode: In-FreqConvM (in Frequency Conversion Mode), Not In-FreqConvM
(Not in Frequency Conversion Mode)
Not In-FreqConvM (Not in Frequency Conversion Mode): In normal working mode.
In-FreqConvM (Frequency Conversion Mode): The output frequency is determined by the frequency and
voltage set by the user. It is not aected by the input and will not cause an alarm.