4. Operation
5. Click the Bypass Setup icon to modify the following values and select the conguration to be changed/saved. Click
the Back icon to return to the previous window, or click the Home Page icon to jump to the main page.
Bypass Volt Prot Lower Limit (%): When the dierence between the bypass voltage and the rated voltage exceeds
the lower threshold for the bypass voltage, the system determines that the bypass voltage is abnormal and that
bypass is unavailable. The value can be -10%, -20%, -30% or -40%. The default value is -40%.
Bypass Volt Prot Limit (%): When the dierence between the bypass voltage and the rated voltage exceeds the
upper threshold for the bypass voltage, the system determines that the bypass voltage is not normal and that bypass is
unavailable.
Notes:
• When the input voltage level is 120V, the value range is 10%, 15%, 20% and 25% (default).
• When the input voltage level is 127V, the value range is 10%, 15% and 20% (default).
Bypass Frequency Tracking Range: When the dierence between the bypass input frequency and the rated
frequency is greater than this value, the system determines that the bypass frequency is not normal and that bypass
is unavailable. The value range is 1%, 2%, 4%, 5% and 10% (default).
Figure 4-29: Bypass Setup
6. Click the Password icon to enter the user password setting interface. Input the old password and the new password
twice, as requested on the display, Then, click SaveCong to conrm the change. The password format is six
numbers. Click the Back icon to return to the previous window, or click the Home Page icon to jump to the main
page. Password Lock Time (min) can be set to a minimum of 1 minute and a maximum of 120 minutes.
Figure 4-30: Password Setup Interface