3. Installation and Wiring
3.13 Dual Input (Mains and Bypass) Connections
M/1R PRIMARY (Mains) INPUT CONNECTION OUTPUT and BATTERY CONNECTION
B/2R SECONDARY- BYPASS (Bps) INPUT Output-L1: Output Phase L1
Mains-L1: Primary input Phase L1 Output-L2: Output Phase L2
Mains-L2: Primary input Phase L2 Output-L3: Output Phase L3
Mains-L3: Primary input Phase L3 Output-N: Output Neutral
Input-N: Input Neutral for primary and secondary input GND: Grounding
Bps-L1: Secondary input Phase L1 BAT+: Positive terminal of the batteries string
Bps-L2: Secondary input Phase L2 BATN: Neutral terminal of the batteries string
Bps-L3: Secondary input Phase L3 BAT-: Negative terminal of the batteries string
WARNING: In the case of dual input operation, ensure the shorting jumper between each input
line has been removed. The AC input and the AC bypass supplies must be referenced to the same
neutral point.
Choose the appropriate power cable (refer to Table 3.2 above).