7. Communications
7.3 USB Communication Port Denition
Notes:
• The USB, RS-232 and RS-485 interfaces cannot be used simultaneously. Only one interface (USB, RS-232, or RS-485) may be
used at a time. Using any of these interfaces does not interfere with the use of the WEBCARDLXMINI.
• These three communication ports use a MODBUS protocol. Refer to the S3M10-20kVA 3-Phase MODBUS Owner’s Manual. The
MODUBS manual may be downloaded from the specic S3M10-20K UPS model page at Tripplite.Eaton.com.
The USB communication port is a USB Type-B female connector.
Connections Between the Connected Computer’s USB Port and UPS System’s USB Port
Computer USB Port UPS USB Port Description
Pin 1 Pin 1 Computer: +5V
Pin 2 Pin 2 Computer: DPLUS signal
Pin 3 Pin 3 Computer: DMINUS signal
Pin 4 Pin 4 Signal ground
Available Functions of the USB Port
Monitor UPS power status
Monitor UPS alarm info
Monitor UPS running parameters
Timing o/on setting
One-to-one communication, UPS to computer, at a distance less than 1.5 m
USB Communication Data Format
Baud rate: 9600 bps
Byte length: 8 bit
End bit: 1 bit
Parity check: None