3. Installation and Wiring
3.6 LCD Control Panel, LEDs and Alarms
3.6.1 Introduction: LCD Display
For detailed information on LCD control panel functions, refer to sections 4.3.2 LCD Control Panel Introduction and
4.3.3 Main Page: Default Display.
1
Alarm LED
2
Bypass LED
3
Battery LED
4
Inverter LED
5
Touchscreen LCD Screen, 5 in. (127 mm)
6
EPO Button (the button must be pressed for at least
3 seconds to activate EPO)
3.6.2 Introduction: Audible Alarms and LEDs
Audible Alarms Display LEDs
Alarm
Status
Mutable
On/O
Alarm Bypass Battery Inverter
UPS
Modes
UPS Initialization
Beeps,
Only Once
No
Blink/
0.5 Second
Blink/
0.5 Second
Blink/
0.5 Second
Blink/
0.5 Second
UPS Online Mode (Normal) No Beeps No Beeps OFF OFF OFF ON
UPS Battery Mode
Beeps/
2 Seconds
Yes OFF OFF ON OFF
UPS Battery Test Mode Beeps No Beeps OFF OFF ON OFF
UPS ECO Mode No Beeps No Beeps OFF ON OFF OFF
UPS Standby Mode No Beeps No Beeps OFF OFF OFF OFF
UPS Static Bypass Mode No Beeps No Beeps OFF ON OFF OFF
UPS Maintenance Bypass
Mode
No Beeps No Beeps OFF ON OFF OFF
UPS Frequency Converter
Mode
No Beeps No Beeps OFF OFF OFF ON
Overload
(Bypass Mode or Battery
Mode)
Beeps/
1 Second
Yes OFF ON ON OFF
1
3
2
4
5
6