3. Installation and Wiring
3.14 UPS Installation for Parallel Systems
WARNING: Installation and wiring must be performed in accordance with local codes/regulations
andinstalledusingthefollowinginstructionsbyaqualiedelectricalservicetechnicianonly.
Cabinet Installation
Connect the UPS for parallel installation per the diagram below.
Ensure each UPS input breaker is in “o” position and there is no output from any connected UPS. Battery groups can be
connected separately or in parallel, which means the system itself provides both separate battery and common battery.
WARNING!
Make sure the N, L1, L2 and L3 lines are correct and grounding is well connected.
3.14.1 Parallel Cable Installation
Shielded and double-insulated control cables available must be interconnected in a ring conguration between UPS
units as shown in Figure 3-18. The ring conguration ensures high reliability of the control. Use only the parallel cables
supplied.
Figure 3-18: Parallel Cable Installation
AC INPUT
AC OUTPUT