28
3. Installation and Wiring
Table 3.5: Battery Cabinet Batteries and Breakers. All battery cabinets are ISTA-3B tested.
Battery Cabinet
Model
Batteries Included
Battery Quantity and Ah Ca-
pacity
Breakers Fuses
BP240V09 / 09K Yes 80 x 9Ah 1 x 125A, 3 Pole 2 x 160A
BP240V09-NIB No Designed for 80 x 9Ah 1 x 125A, 3 Pole 2 x 160A
BP240V40 Yes 20 x 40Ah 1 x 250A, 3 Pole 4 x 250A
BP240V40L Yes 40 x 40Ah 1 x 250A, 3 Pole 4 x 250A
BP240V40-NIB No
Designed for 20
(CSB GP12400i) x 40AH
1 x 250A, 3 Pole 4 x 250A
BP240V40L-NIB No
Designed for 40
(CSB GP12400i) x 40Ah
1 x 250A, 3 Pole 4 x 250A
3.12 Single Input Power Cable Connection
Once the equipment has been positioned and secured, connect the power cables as described in the procedure below.
Verify the UPS is totally isolated from its external power source and that all power isolators of the UPS are open. Ensure
they are electrically isolated, and post any necessary warning signs to prevent their independent operation.
Remove the terminal block cover to access the UPS system’s input, output and grounding connection terminals. Then
connect the wires according to the terminal block diagram shown below. Connect the grounding/earthing wires rst
when making other wire connections.
Notes:
Ensure the wires are connected tightly and securely to the terminals.
Install the output breaker between the output terminal and the load. The breaker should be qualied with leakage current protective
function.
Cabling should be protected by exible conduit and routed through the appropriate knockouts in the terminal block cover.
Be sure to also add an equipotential bonding wire between the UPS and the external battery cabinets.