Weil-McLain EVERGREEN PRO EVG-299 Gas Boiler Evergreen High Efficiency Gas Boiler

User Manual - Page 75

For EVERGREEN PRO EVG-299.

PDF File Manual, 136 pages, Read Online | Download pdf file

EVERGREEN PRO EVG-299 photo
Loading ...
Loading ...
Loading ...
Screensshownabovearetypicalonly.
Actualscreensdependoncontrol
settingschosen.
Part number 550-100-211/0122
– 75 –
220 /29 9/3 00 /39 9 

BoilerModel,AltitudeandFuelTypearecriti-
cal
settings.Failure to set correctly could result in
severe personal injury, death or substantial property
damage.
1. Access contractor menus by pressing and holding the UP and
DOWN arrow keys at the same time for 7 seconds.
2. See the following pages for explanations of control setting
options.
MENUITEM PURPOSE
More
information
USER MODE
y e default for this setting is BASIC mode. Screens shown
in this manual assume the USER MODE is set to BASIC. For
advanced features available in ADVANCED mode, see the
Evergreen Advanced Manual.
BOILER
SETTINGS
y Set/change boiler model, control type,
high altitude setting, ODT sensor require-
ment, manual reset, high limit and WWSD
temperature settings, outdoor sensor temp
adjustment, circulator exercising, freeze
protection setup, and restore to factory
default option.
See page 76
PRIORITY 1
y ese settings control operating tempera-
tures and behaviors for systems that are
assigned to “PRIORITY 1.
See page 77
PRIORITY 2
y ese settings control operating tempera-
tures and behaviors for systems that are
assigned to “PRIORITY 2.
See page 77
PRIORITY 3
y ese settings control operating tempera-
tures and behaviors for systems that are
assigned to “PRIORITY 3.
See page 77
ASSIGN INPUTS
y ese settings assign Priority 1, 2 or 3 to
each of the three inputs to the Evergreen
control.
See page 78
DIAGNOSTICS
y Use to review current and historical infor-
mation including previous lockouts.
See page 80
MAINTENANCE
INFO
y Used to set contractor contact information,
boiler information and maintenance dates.
See page 85
SET TIME &
DATE
y Use to set date and time — important since
fault occurrences are date/time stamped.
None
Figure74 Evergreen control menu access — accessing contractor menus