Weil-McLain EVERGREEN PRO EVG-299 Gas Boiler Evergreen High Efficiency Gas Boiler

User Manual - Page 74

For EVERGREEN PRO EVG-299.

PDF File Manual, 136 pages, Read Online | Download pdf file

EVERGREEN PRO EVG-299 photo
Loading ...
Loading ...
Loading ...
Part number 550-100-211/0122
– 74 –
Figure72 Evergreen control settings available in BASIC MODE (see Advanced Manual for ADVANCED MODE settings)

Figure73 System types available in BASIC MODE (each option shown with factory settings)
AvailablesettingsfromCONTRACTORMENU
BoilerSettingsMenu Priority2menu AssignInputsmenu
y Boiler Model y Inputs Assigned (non-selectable)
Input1:TT1
y Control Type y System Type y Priority 1, 2 or 3
y High Altitude y Target Mod Sensor (non-selectable) y Source (TT1 or 0-10v)
y LP Gas y Target Adjust (non-selectable) y AUX PUMP/OUTPUT
y ODT Sensor Exempt y Supply Max y O
y Manual Reset High Limit Temp y Supply Min (not available for DHW) *
y WWSD Temp y OD Reset Max (or Volts for Max) *
Input2:TT2andInput3:TT3
y Adjust Outdoor y OD Reset Min (or Volts for Min) * y Priority 1, 2 or 3
y Circulator Exercising y Boost Time * y AUX PUMP/OUTPUT
y Freeze Protect Circs y O
y Reset Factory Default
Priority3menu
y Inputs Assigned (non-selectable)
Diagnosticsmenu
Priority1menu
y System Type
y See Figure80,page80 for details.
y Inputs Assigned (non-selectable) y Target Mod Sensor (non-selectable)
y System Type y Target Adjust (non-selectable)
MaintenanceInfomenu
y Target Mod Sensor (non-selectable) y Supply Max
y See Figure85,page85 for details.
y Target Adjust (non-selectable) y Supply Min (not available for DHW) *
y Supply Max y OD Reset Max (or Volts for Max) *
SetDateandTimemenu
y Supply Min (not available for DHW) * y OD Reset Min (or Volts for Min) *
y See Figure85,page85 for details.
y OD Reset Max (or Volts for Max) * y Boost Time *
y OD Reset Min (or Volts for Min) * * ese items only appear in the menus if Target Adjust is active.
y Boost Time *
SystemType
8-Character
Abbreviation
3-Character
Abbreviation
Supply Max
°F
OD Reset
Min °F
Supply
Min °F
OD Reset
Max °F
Run
Boiler Pump
Run AUX
PUMP/
OUTPUT
Fan-coil FAN-COIL
FCL 180 0 140 70 YES YES
Finned Tube
Baseboard
FIN BASE
FTB 180 0 130 70 YES YES
Cast Iron Baseboard IRONBASE
CIB 180 0 120 70 YES YES
Cast Iron Radiators RADIATOR
CIR 180 0 120 70 YES YES
Radiant - slab on grade RAD SLAB
RSG 120 0 80 70 YES YES
Radiant - thin slab RAD SLAB
RTS 140 0 80 70 YES YES
Radiant - below oor
(staple up)
RADFLOOR
RSU 160 0 90 70 YES YES
Radiant - above oor
(sleeper system)
RADFLOOR
RAF 140 0 90 70 YES YES
Domestic Hot Water DOMESTIC
DHW 180 N/A N/A N/A NO NO
Custom (user dened)
XXXXXXXX
(user input)
rst three of
user input
180 0 70 70 YES YES
220 /29 9/3 00 /39 9 