– 70 –
 B
2-or3-ZoneSPACE H EATING(Circulatorswithoutcirculatorrelays)|DHW
(Direct-piped)
EVG
(in order of WiZArd sequences)
REDvAlue must be set or verified
d — defAult AcceptAble; chAnge only
if desired
BOILER SET TI NGS
BOILER MODEL
Verifymodelnumberiscorrect
WWSDTEMP
Default(70°F)orasrequired
HIGHALTITUDE
Settoaltitudeifover2,000feet
(Assign to PRIORITY 1) (Note 1)
WHATISTHEUSEOFINPUT/OUTPUT1?
HEAT/DHWDEMAND
WHATPRIORITYISINPUT#1?
select
PRIORITY1
WHATSYSTEMTYPEISINPUT/OUTPUT1?
DHW(D)
TARGETMODSENSOR
BOILEROUT(D)
TARGETADJUST
NONE(D)
SUPPLYMAX
D (or change if desired)
RUNBOILERPUMP?
NO(D)
RUNAUXPUMP/OUTPUT?
D (not applicable)
IN PU T/OUT PU T 2 (Assign to PRIORITY 2)
WHATISTHEUSEOFINPUT/OUTPUT2?
HEAT/DHWDEMAND
WHATPRIORITYISINPUT#2?
PRIORITY2
WHATSYSTEMTYPEISINPUT/OUTPUT2?
Selectcorrectsystemtype
TARGETMODSENSOR
SYSTEMSUPPLY(D)
TARGETADJUST
ODT(D)
(outdoor sensor must be installed)
SUPPLYMAX
D (or change if desired)
SUPPLYMIN
D (or change if desired)
ODRESETMAX
D (or change if desired)
ODRESETMIN
D (or change if desired)
BOOSTTIME
D (or change if desired)
RUNBOILERPUMP?
YES(D)
RUNAUXPUMP/OUTPUT?
D (not applicable)
IN PU T/OUT PU T 3 (Assign to PRIORITY 2)
IfPRIORITY2isassigned,nofurtherstepsarerequired.IfPRIORITY3
isassigned,repeatthestepsfromINPUT/OUTPUT2,above.

P1MAXONTIME
D (or change if desired)
P2MAXONTIME
D (or change if desired)
P2MINONTIME
D (or change if desired)
P3MINONTIME
D (not applicable)

ENTERTIME,DATEANDMAINTENANCEINFORMATIONASPROMPTED
Boiler Model, Altitude and Fuel Type are critical
settings.
Failure to set correctly could result in severe
personal injury, death or substantial property damage.
Incorrect setup or piping can result in severe personal
injury, death or substantial property damage.
Use primary/secondary piping or equivalent ONLY. Do
notusedirect-connectsystempiping.
Verify that the correct system type is selected on the con-
trol and that operating temperature settings are suitable
for the system. System and structural damage can occur
if temperatures are too high.

y Space heating with multiple zones.
y Zoning with circulators using EVG control outputs to
operate zone circulators (3 zones if space heating only;
or 2space heating zones plus DHW.
y DHW piped directly to the boiler.
y DHW priority — space heating is disabled during call
for heat from water heater.

y See the table at right for required and optional settings.
y e sequence in the table follows the WIZARD.
y If not using the WIZARD, follow instructions elsewhere
in this manual to enter the settings manually.

Provide an external relay and external power
to any circulator if its load rating exceeds 2.2
amps FLA, 3.6amps locked rotor, or 16.4 amps
in rush.
y Piping must be primary/secondary as shown.
y DHW circulator must be selected to handle the pressure
drop through the boiler, water heater and piping. DHW
circulator supplied by installer.
y For some large indirect water heaters, the required ow
rate may require piping the water heater dierently.
y e control settings in table at right provide DHW
priority — space heating will be discontinued during
a call for DHW.
y Zone circulators supplied by installer. For alternate zone
wiring using a zone controller, see page61.
BOILER
y Boiler circulator shipped loose with boiler.
y Follow all instructions in this manual for piping boiler
and system.
Note1: IfDHWisnotused, provide a third space heating
zone by setting up INPUT/OUTPUT1 exactly the
same as INPUT/OUTPUT2. Make sure to assign
INPUT/OUTPUT1 to PRIORITY2. is is because
PRIORITY2 is factory preset for space heating
congurations. Wire the third zone thermostat to
P11–4&5 and its circulator to P9–1,4&5.