ALL vent and air pipes require a BIRD SCREEN at each termination. Most kits do not include
the bird screens. Purchase bird screens separately from Weil-McLain or vent kit supplier if
not included. [Note — bird screening is integral to the 3” and 4” PVC Weil-McLain sidewall
vent cap, purchased separately. No additional screening is required.]
Figure24  — Use only the materials listed below, ensuring that all materials meet
local codes (see Figure 111, page 117 for part/kit numbers)
Part number 550-100-211/0122
– 21 –
220 /29 9/3 00 /39 9 
Item Material
Standardsforinstallationsin:
UnitedStates Canada(Note 2)
Plasticpipingmaterials Ventorairpiping Ventpiping Airpiping
Ventorairpipe
&
ttings
PVC schedule 40 (Note 1) ANSI/ASTM D1785/UL1738/ULC S636 ULC S636
PVC, PVC-DWV,
CPVC or
polypropylene
PVC-DWV schedule 40 (Note 1) ANSI/ASTM D2665 N/A
CPVC schedule 40 (Note 1) ANSI/ASTM F441 / ULC S636 ULC S636
PVC&ABSpipe
cement&primer
PVC (Note 1) ANSI/ASTM D2564 / F656 / UL1738 ULC S636
Use only cement
and primer suitable
for piping material
used
CPVC (Note 1) ANSI/ASTM F493 ULC S636
CPVC to PVC transition
Use only cement and primer suitable
for piping material used
ULC S636
Polypropylene
ventpipe,ttings,
terminationsand
cement
Simpson-Duravent—Obtain all materials from M&G
Simpson-Duravent
CentrothermEcoSystemsInnoFlue®Single-wall
—Obtain all materials from Centrotherm
(Note: See page 117 for correct appliance adapters to be used.)
See manufacturer’s literature for detailed
information
MUST USE LOCKING COLLAR
ON EVERY JOINT
ULC S636
PVC, PVC-DWV,
CPVC or
polypropylene
AL29-4Cstainlesssteelpipingmaterials
Ventpipe
AL29-4C
stainless
steel
Heat Fab, Inc. — Saf-T-Vent
®
Z-Flex, Inc. — Z-Vent
Dura-Vent — FasNSeal™
Metal-Fab, Inc. — CORR/GUARD
Certied for Category IV and direct
vent appliance venting
Certied for Category IV and direct vent
appliance venting
Weil-McLainstainlesssteelbirdscreens,3”or4”(purchase separately) — see Figure 111, page 117 for part numbers
Note 1: Weil-McLain concentric vent kits are made from PVC
pipe and ttings.
Note 2: System 636 PVC concentric terminations utilize PVC
pipe/ttings certied to ULC S636.
If ULC S636 compliance is required, use only System
636 pipe, ttings and cement.
If UL1738 compliance is required, use only System
1738 pipe, ttings and cement.
DO NOT mix piping from dierent pipe manufactur-
ers unless using adapters specically designed for the
purpose by the manufacturer.
Every joint on polypropylene vent piping must include
a locking collar.
DO NOT use cellular core PVC (ASTM F891), cellular
core CPVC, or Radel
®
(polyphenolsulfone) in venting
systems.
DO NOT cover non-metallic vent pipe and fittings
with thermal insulation.
ADAPTERS — AL29-4C piping — Install a PVC-to-stainless
adapter supplied by the AL29-4C stainless pipe manufac-
turer at the 4” PVC boiler vent connection. Can not be uesd
with Weil-McLain termination plate or concentric termina-
tion.
ADAPTERS — Polypropylene piping — Provide adapters
from polypropylene pipe to the 4” PVC connections at the
boiler and at terminations, if required (Weil-McLain side-
wall plate, for example).
ADAPTERS — If using 3” piping, where approved for the
application, provide adapters for the 4” PVC boiler con-
nections and at the terminations, if required (Weil-McLain
sidewall plate, for example).
For PVC – USE SWEEP ELBOWS FOR ALL VENT AND AIR PIPING — DO NOT use
short radius elbows for vent or air piping. Boiler performance could be affected.