Menu Function Default Range Description
H-25
RS-485 communication
baud rate.
0 0–3
0: 115200, 1: 38400, 2: 19200, 3: 9600.
Leave it as the default.
H-26
RS-485 communication
address.
1 1–255
H-31
Enter the fleet mode
when opening the boom
gate by remote control.
0 0, 1 See Advanced Settings Details.
H-33
Learn the up and down
limits according to the
defined speed.
0 0–2
0: Learn the up and down limits.
1: Only learn the up limit
(recommended).
2: Only learn the down limit.
H-34
Adjust the up and down
limits manually.
None None
Only manually adjust the up and down
limits.
H-35
Adjust the up limit
manually.
None None
Only manually adjust the up limit.
Recommended for fence boom gate.
H-36
Adjust the down limit
manually.
None None
Only manually adjust the down limit.
Recommended when there is eave.
H-38 Coil signal buzzer. 0 0, 1 0: Buzz. 1: Not buzz.
H-45
Speed of auto delay
closing.
50
15
100
Refer to this value when F-10 >0.
H-46
Auto opening time if low
voltage occurs.
0 0–50
0 means the boom gate does not open
when in low voltage. Unit: 0.1 seconds.
For example, when you set the time to
20, 2 seconds (20 × 0.1) after the
voltage is lower than the defined
threshold, the boom gate will
automatically open.
H-47
Auto opening when
reaching the low voltage
threshold.
21 1522
The boom gate automatically opens
when the voltage meets the defined
threshold. Unit: volt.
Advanced Settings Details
H-02 quick commissioning
Table 3-8 Commissioning mode
Commissioning
Mode
Opening/Closing Speed
(second)
Commissioning
Mode
Opening/Closing Speed
(second)
3E1.2 1.2 3E1.5 1.5
3E2 2 3E3 3
3E4 4 3E5 5
3E6 6