13
SPECIFICATIONS
Product Specifications Multi-Zone Concealed Ducted
PERFORMANCE RATINGS Multizone ‑ The Insider™ Concealed Ducted Heat Pumps
9k 12k 18k
INDOOR MODEL FPHFD09A3A FPHFD12A3A FPHFD18A3A
SPECIFICATIONS
CAPACITY COOLING (RATED) Btu 9,000 12,000 18,000
CAPACITY HEATING (RATED) Btu 10,000 12,500 19,000
MOISTURE REMOVAL Pts/h 1.9 3.2 3.2
Max Airflow (@0.1 E.S.P.) CFM 294 353 529
SOUND RATING (MAX.‑MIN.) dB‑A 33/26 34/27 35/31
ELECTRICAL DATA
POWER SOURCE V, Ø, Hz 208‑230, 1, 60 208‑230, 1, 60 208‑230, 1, 60
POWER AND COMMUNICATION CABLE TYPE 14/4 AWG
600V THHN
14/4 AWG
600V THHN
14/4 AWG
600V THHN
REFRIGERATION SYSTEM
CONNECTIONS Flare Flare Flare
LIQUID LINE O.D. in 1/4 1/4 1/4
SUCTION LINE O.D. in 3/8 3/8 1/2
DIMENSIONS & WEIGHT
W X H X D in 35 7/8 x 7 7/16 x 17 35 7/8 x 7 7/16 x 17 46 7/16 x 7 1/2 x 17 1/2
NET WEIGHT lbs 45.2 45.2 66.2
SHIPPING WEIGHT lbs 51.8 51.8 77.2
NOTE:
1. Test conditions
Cooling: Indoor: DB80°F(26.7)/ WB67°F(19.4) Outdoor: DB95°F(35)/ WB75°F(23.9)
Heating: Indoor: DB70°F(21.1)/ WB60°F(15.6) Outdoor: DB47°F(8.3)/ WB43°F(6.1)
2. The Sound Pressure Level is based on the following conditions:
Indoor unit
Duct:
Measure the noise value of the point 4.6ft(1.4m) below the unit and 3.3ft(1.0m) high from the ground.
3. The above data was measured in an anechoic chamber. Please take into consideration reflected sound of your specific
application environment.
4. All specifications are subjected to change by the manufacturer without prior notice.