Friedrich 1198788 Floating Air Series 24000 BTU Dual Zone Mini Split System with 2x 9000 BTU Wall Mounted Unit and Outdoor Unit

User Manual - Page 117

For 1198788.

PDF File Manual, 244 pages, Read Online | Download pdf file

1198788 photo
Loading ...
Loading ...
Loading ...
117
CORRECTION FACTORS
Piping Length Correctiion Factor
5(15) 14( 10) 23( 5) 32(0) 44.6(7)
OUTDOOR TEMPERATURE
50(10) 59(15)
Correction factor(humidity rate 85% RH) 0.95 0.95 0.9 2 0.8 4 1.0 1.0 1.0
Correction Factor
NOTE:
Correction factors according to defrosting operation
The heating capacity in the preceding paragraph excludes the condition of the frost or the
or the defrosting operation period. In consideration of the frost or the defrosting operation,
the heating capacity is corrected by the equation below.
Corrected heating capacity = Defrost Correction factor x unit capacity
[°F(°C) DB]
Correction Factor is not valid when the outdoor unit is covered or encapsulated with snow.
Loading ...
Loading ...
Loading ...